    The S506-2-R from Eaton carries 2 A, uses a time-delay element, in a glass body.

    Technical Data

    ParameterRating
    ParameterValue
    Orderable part numberS506-2-R (BK- prefix = 100 pcs carton, BK1- = 1,000 pcs polybag)
    Typical melting I2t31.6 A2s
    AgencycURus (E19180, JDYX2); SEMKO; VDE; BSI; IMQ; PSE (JET); KC; CCC
    Design standardIEC 60127-1 and 60127-2
    Time-delay classT (time-lag)
    Current rating2 A
    Typical drop77 mV at rated current
    Un (rated)250 Vac
    Power dissipation0.15 W
    Body / package5 x 20 mm glass tube, nickel-plated brass end caps
    Typical DC cold resistance0.0333 Ohm
    Interrupting rating35 A at 250 Vac, 50 Hz

    Practical Notes

    • Interrupting capability is 35 A at 250 Vac, 50 Hz — confirm the circuit's prospective fault current stays below this.
    • Time-delay element rides through motor starting and capacitive inrush without nuisance opening.
    • Startup surges of several times rated current are tolerated for a short window.
    • Glass body lets you inspect the element after a fault.
    • Best kept for lower fault-current circuits where visual diagnosis matters.
    • Do not upsize beyond 2 A to stop nuisance trips — fix the cause instead.

    Application Scenarios

    Common installation contexts include:

    • EV
    • transformer

    Buying Notes

    Order code S506-2-R from Eaton, supplied in 5 x 20 mm glass tube, nickel-plated brass end caps. Confirm the exact suffix before release.

    Questions and Answers

    Is the S506-2-R fast-acting or time-delay?

    It is time-delay. It tolerates short inrush surges.

    Can the S506-2-R be used on a higher fault-current circuit?

    No — its interrupting rating is 35 A at 250 Vac, 50 Hz. Choose a part whose breaking capacity exceeds the prospective fault current.