Eaton S506-4-R 4 A 250 Vac Time-Delay Glass Tube Fuse
Eaton S506-4-R 4 A 250 Vac Time-Delay Glass Tube Fuse

Eaton S506-4-R 4 A 250 Vac Time-Delay Glass Tube Fuse

Share
pEaton S506-4-R — 4 A, 250 V, time-delay glass cartridge fuse, 40 A at 250 Vac, 50 Hz interrupting./p
    • Product Details
    • Download

    Eaton S506-4-R 4 A 250 Vac Time-Delay Glass Tube Fuse

    The S506-4-R from Eaton carries 4 A, rated 250 Vac, uses a time-delay element, in a glass body.

    Technical Data

    ParameterRating
    ParameterValue
    Orderable part numberS506-4-R (BK- prefix = 100 pcs carton, BK1- = 1,000 pcs polybag)
    Typical melting I2t71.8 A2s
    Dissipation at rating0.27 W
    Time-delay classT (time-lag)
    AgencycURus (E19180, JDYX2); SEMKO; VDE; BSI; IMQ; PSE (JET); KC; CCC
    Current rating4 A
    Rated voltage250 Vac
    Interrupting rating40 A at 250 Vac, 50 Hz
    Typical voltage drop67 mV at rated current
    Body5 x 20 mm glass tube, nickel-plated brass end caps
    Typical DC cold resistance0.0139 Ohm
    Design standardIEC 60127-1 and 60127-2

    Practical Notes

    • Interrupting capability is 40 A at 250 Vac, 50 Hz — confirm the circuit's prospective fault current stays below this.
    • Time-delay element rides through motor starting and capacitive inrush without nuisance opening.
    • Startup surges of several times rated current are tolerated for a short window.
    • Glass body lets you inspect the element after a fault.
    • Best kept for lower fault-current circuits where visual diagnosis matters.
    • Working voltage must stay at or below 250 Vac; a lower-rated part is not a safe substitute.
    • Do not upsize beyond 4 A to stop nuisance trips — fix the cause instead.

    Application Scenarios

    Common installation contexts include:

    • UPS
    • EV
    • surge

    Questions and Answers

    What are the ratings of the S506-4-R?

    4 A continuous at 250 Vac, interrupting rating 40 A at 250 Vac, 50 Hz.

    Is the S506-4-R fast-acting or time-delay?

    It is time-delay. It tolerates short inrush surges.

    Can the S506-4-R be used on a higher fault-current circuit?

    No — its interrupting rating is 40 A at 250 Vac, 50 Hz. Choose a part whose breaking capacity exceeds the prospective fault current.

    Shenzhen Gaorunxin Technology Co., Ltd

    Online message

    Shenzhen Gaorunxin Technology Co., Ltd

    Related Products