| Parameter | Rating |
|---|---|
| Parameter | Value |
| Orderable part number | S506-5-R (BK- prefix = 100 pcs carton, BK1- = 1,000 pcs polybag) |
| Rated voltage | 250 Vac |
| Dissipated power at rating | 0.30 W |
| Design standard | IEC 60127-1 and 60127-2 |
| Body / package | 5 x 20 mm glass tube, nickel-plated brass end caps |
| Typical melting I2t | 142.5 A2s |
| Time-delay class | T (time-lag) |
| Typical DC cold resistance | 0.0098 Ohm |
| Interrupting rating | 50 A at 250 Vac, 50 Hz |
| Typical drop | 60.5 mV at rated current |
| Current | 5 A |
| Agency | cURus (E19180, JDYX2); SEMKO; VDE; BSI; IMQ; PSE (JET); KC; CCC |
Common installation contexts include:
Order code S506-5-R from Eaton, supplied in 5 x 20 mm glass tube, nickel-plated brass end caps. Confirm the exact suffix before release.
What are the ratings of the S506-5-R?
5 A continuous at 250 Vac, interrupting rating 50 A at 250 Vac, 50 Hz.
Is the S506-5-R fast-acting or time-delay?
It is time-delay. It tolerates short inrush surges.
Can the S506-5-R be used on a higher fault-current circuit?
No — its interrupting rating is 50 A at 250 Vac, 50 Hz. Choose a part whose breaking capacity exceeds the prospective fault current.