Eaton S506-50-R 50 mA 250 Vac Time-Delay Glass Tube Fuse
Eaton S506-50-R 50 mA 250 Vac Time-Delay Glass Tube Fuse

Eaton S506-50-R 50 mA 250 Vac Time-Delay Glass Tube Fuse

Share
pEaton S506-50-R — 50 mA, 250 V, time-delay glass cartridge fuse, 35 A at 250 Vac, 50 Hz interrupting./p
    • Product Details
    • Download

    Eaton S506-50-R 50 mA 250 Vac Time-Delay Glass Tube Fuse

    Eaton S506-50-R 50 mA 250 Vac Time-Delay Glass Tube Fuse belongs to the Eaton range. It carries 50 mA, rated 250 Vac, uses a time-delay element, in a glass body.

    Technical Data

    ParameterRating
    ParameterValue
    Orderable part numberS506-50-R (BK- prefix = 100 pcs carton, BK1- = 1,000 pcs polybag)
    Design standardIEC 60127-1 and 60127-2
    Voltage drop (typical)800 mV at rated current
    AgencycURus (E19180, JDYX2); SEMKO; VDE; BSI; IMQ; KC; CCC
    Dissipation at rating0.04 W
    Cold resistance (typical)9.24 Ohm
    Melting I2t (typical)0.0095 A2s
    Voltage rating250 Vac
    Interrupting rating35 A at 250 Vac, 50 Hz
    Body5 x 20 mm glass tube, nickel-plated brass end caps
    Current rating50 mA
    Time-delay classT (time-lag)

    Design Notes

    • Interrupting capability is 35 A at 250 Vac, 50 Hz — confirm the circuit's prospective fault current stays below this.
    • Time-delay element rides through motor starting and capacitive inrush without nuisance opening.
    • Startup surges of several times rated current are tolerated for a short window.
    • Glass body lets you inspect the element after a fault.
    • Best kept for lower fault-current circuits where visual diagnosis matters.
    • Working voltage must stay at or below 250 Vac; a lower-rated part is not a safe substitute.
    • Do not upsize beyond 50 mA to stop nuisance trips — fix the cause instead.

    Where It Is Used

    Typical places this fuse turns up:

    • EV
    • transformer

    Common Questions

    What are the ratings of the S506-50-R?

    50 mA continuous at 250 Vac, interrupting rating 35 A at 250 Vac, 50 Hz.

    Is the S506-50-R fast-acting or time-delay?

    It is time-delay. It tolerates short inrush surges.

    Can the S506-50-R be used on a higher fault-current circuit?

    No — its interrupting rating is 35 A at 250 Vac, 50 Hz. Choose a part whose breaking capacity exceeds the prospective fault current.

    Shenzhen Gaorunxin Technology Co., Ltd

    Online message

    Shenzhen Gaorunxin Technology Co., Ltd

    Related Products