| Parameter | Rating |
|---|---|
| Parameter | Value |
| Orderable part number | S506-V-5-R (TR2- = 1,500 pcs on reel; BK- = 100 pcs carton) |
| Rated voltage | 250 Vac |
| Lead spacing (dim B) | 38.1 mm +/- 0.38 (BK-) / 15.8 mm +/- 2.0 (TR2-) |
| Typical DC cold resistance | 0.0098 Ohm |
| Melting I2t (typical) | 142.5 A2s |
| Typical drop | 60.5 mV at rated current |
| Design standard | IEC 60127-1 and 60127-2, T time-lag |
| Body diameter | 5.54 mm +/- 0.20 mm |
| Interrupting rating | 50 A at 250 Vac, 50 Hz |
| Physical form | 5 x 20 mm glass tube, nickel-plated brass end caps |
| In (rated) | 5 A A |
| Overall length (cap to cap) | 21.1 mm +/- 0.81 mm |
| Lead diameter (dim A) | 0.81 mm tinned copper |
| Agency | cURus (E19180, JDYX2); SEMKO; VDE; BSI; IMQ; PSE (JET); KC; CCC |
Is the S506-V-5-R fast-acting or time-delay?
It is time-delay. It tolerates short inrush surges.
Can the S506-V-5-R be used on a higher fault-current circuit?
No — its interrupting rating is 50 A at 250 Vac, 50 Hz. Choose a part whose breaking capacity exceeds the prospective fault current.