    Built by Eaton, the S520-10-R carries 10 A, rated 420 Vac, uses a fast-acting element, in a ceramic body.

    Technical Data

    ParameterRating
    ParameterValue
    Orderable part numberS520-10-R (BK- = 100 pcs carton, BK1- = 1,000 pcs polybag; S520-V-10-R for axial leads)
    Rated current10 A
    Typical melting I2t155 A2s (measured at 10 In)
    Interrupting rating at 250 Vac1500 A
    AgencyUR E19180 (JDYX2); TUV T 50484820 02
    Interrupting rating at 420 Vac200 A
    Body5 x 20 mm ceramic tube, nickel/silver plated brass ends
    Operating temperature-55 C to +125 C with derating
    Voltage rating420 Vac
    Dissipation at rating1.11 W
    Typical DC cold resistance8 mOhm
    Typical voltage drop111 mV at rated current

    Selection Notes

    • Interrupting capability is 1500 A — confirm the circuit's prospective fault current stays below this.
    • Fast element suits resistive and semiconductor loads rather than motors with high inrush.
    • Because it opens within milliseconds, downstream semiconductors see less let-through energy.
    • Ceramic body holds higher breaking capacity than glass at the same footprint.
    • It is the usual choice where prospective fault current is high.
    • Working voltage must stay at or below 420 Vac; a lower-rated part is not a safe substitute.
    • Do not upsize beyond 10 A to stop nuisance trips — fix the cause instead.

    Typical Applications

    Engineers usually specify it for these duties:

    • PFC
    • surge

    Q&A

    What are the ratings of the S520-10-R?

    10 A continuous at 420 Vac, interrupting rating 1500 A.

    Is the S520-10-R fast-acting or time-delay?

    It is fast-acting. Expect it to open quickly on overload.

    Can the S520-10-R be used on a higher fault-current circuit?

    No — its interrupting rating is 1500 A. Choose a part whose breaking capacity exceeds the prospective fault current.