    The S520-15-R from Eaton carries 15 A, uses a fast-acting element, in a ceramic body.

    Technical Data

    ParameterRating
    ParameterValue
    Orderable part numberS520-15-R (BK- = 100 pcs carton, BK1- = 1,000 pcs polybag; S520-V-15-R for axial leads)
    Operating temperature-55 C to +125 C with derating
    Body / package5 x 20 mm ceramic tube, nickel/silver plated brass ends
    Interrupting rating at 250 Vac1500 A
    Dissipation at rating2.92 W
    Voltage420 Vac
    Typical DC cold resistance6.8 mOhm
    Typical melting I2t220 A2s (measured at 10 In)
    Interrupting rating at 420 Vac300 A
    Current rating15 A
    Typical drop195 mV at rated current
    AgencyUR E19180 (JDYX2); TUV T 50484820 02

    Practical Notes

    • Interrupting capability is 1500 A — confirm the circuit's prospective fault current stays below this.
    • Fast element suits resistive and semiconductor loads rather than motors with high inrush.
    • Because it opens within milliseconds, downstream semiconductors see less let-through energy.
    • Ceramic body holds higher breaking capacity than glass at the same footprint.
    • It is the usual choice where prospective fault current is high.
    • Do not upsize beyond 15 A to stop nuisance trips — fix the cause instead.

    Application Scenarios

    Common installation contexts include:

    • PFC
    • surge
    • transformer

    Buying Notes

    Order code S520-15-R from Eaton, supplied in 5 x 20 mm ceramic tube, nickel/silver plated brass ends. Confirm the exact suffix before release.

    Questions and Answers

    Is the S520-15-R fast-acting or time-delay?

    It is fast-acting. Expect it to open quickly on overload.

    Can the S520-15-R be used on a higher fault-current circuit?

    No — its interrupting rating is 1500 A. Choose a part whose breaking capacity exceeds the prospective fault current.