Eaton SMAJ33CA Transient Voltage Suppressor 33 V
Eaton SMAJ33CA Transient Voltage Suppressor 33 V

Eaton SMAJ33CA Transient Voltage Suppressor 33 V

Share
SMAJ33CA: transient voltage suppressor diode, 33 V standoff, 53.3 V clamp, 7.5 A pulse, 400 W, bidirectional.
    • Product Details
    • Download

    Eaton SMAJ33CA Transient Voltage Suppressor 33 V

    SMAJ33CA at a glance: transient voltage suppressor diode, 33 V standoff, 53.3 V clamp, 7.5 A pulse, 400 W, bidirectional.

    Ratings at a Glance

    ParameterValue
    Orderable part numberSMAJ33CA
    Standoff voltage (VR)33 V
    Leakage current at VR1 uA
    Breakdown voltage at IT36.7 V to 40.6 V
    Test current (IT)1 mA
    Clamping voltage at IPP53.3 V
    Peak pulse current7.5 A
    PolarityBidirectional
    Peak pulse power, 10/1000 us400 W
    PackageSMA (DO-214AC)
    MountingSurface mount
    Operating temperature-55 °C to +150 °C
    QualificationCommercial grade
    RoHSCompliant, halogen free
    Data sheetEaton Technical Data ELX1564

    Outline drawing, pad or lead geometry and the pulse derating curves are
    on the pages of Eaton Technical Data ELX1564; the package line above is the
    body the part is built in.

    What the Numbers Mean

    A transient voltage suppressor is a diode biased so that it stays off at the working voltage and breaks down in a surge. The three numbers that decide whether it fits are the standoff voltage, the breakdown window and the clamping voltage at the pulse current you expect.

    The breakdown window spans 10.63 percent, from 36.7 V to 40.6 V. Design against the minimum, because a part at the bottom of the window starts conducting first.

    At 33 V standing the leakage is at most 1 uA, so the part draws 0.033 mW on the rail. Small, but it is the number that matters on a battery input.

    Within the SMAJ family this is item 62 of 151 in the Eaton catalogue.

    Where This Series Fits

    The part goes across the line after the fuse, with the return path as short as the layout allows. Every centimetre of trace between the connector and the diode adds inductance, and the clamp the circuit sees is the diode clamp plus L di/dt.

    • The standoff voltage is a DC limit. On an AC line the peak of the sine has to stay below it, which for a 120 V RMS line means a part rated well above 170 V.
    • The clamp column is measured at the rated pulse current. At a lower current the residual voltage is lower, which is why a part chosen for a small surge clamps better than its headline number suggests.

    Frequently Asked Questions

    Does the peak pulse power rating apply to any surge?
    No. It is quoted for a 10/1000 microsecond waveform. A shorter pulse allows more current and a longer one less; the derating curve converts between them.

    How do I pick the standoff voltage?
    Above the highest steady-state voltage the line can reach, including regulation, ripple and any temporary overvoltage the standard requires. Then check that the minimum breakdown voltage is still above that level, because production spread moves it down.

    Why is the clamp voltage higher than the breakdown voltage?
    The breakdown is measured at 1 mA; the clamp is measured at the full pulse current, which can be hundreds of amps. The dynamic resistance of the junction adds the difference, and that is why the two columns are never the same number.