Eaton SR-5F-10A-AP 10 A 125 Vac Fast-Acting Subminiature Fuse
Eaton SR-5F-10A-AP 10 A 125 Vac Fast-Acting Subminiature Fuse

Eaton SR-5F-10A-AP 10 A 125 Vac Fast-Acting Subminiature Fuse

Share
pEaton SR-5F-10A-AP — 10 A, 125 V, fast-acting fuse, 50 A at rated voltage, 50 Hz interrupting./p
    • Product Details
    • Download

    Eaton SR-5F-10A-AP 10 A 125 Vac Fast-Acting Subminiature Fuse

    The SR-5F-10A-AP from Eaton carries 10 A, rated 125 Vac, uses a fast-acting element.

    Technical Data

    ParameterRating
    ParameterValue
    Orderable part numberSR-5F-10A-AP (-AP = 1,000 pcs ammo pack, 12.7 mm pitch)
    Dissipation at rating2.00 W
    Typical DC cold resistance0.007 Ohm
    Typical voltage drop200 mV at rated current
    CharacteristicFast-acting (F)
    Maximum power dissipation at 1 In2000 mW
    Interrupting rating50 A at rated voltage, 50 Hz
    Design standardUL 248-14
    BodyRadial leaded, fast-acting, plastic cap and base, UL 94V0
    AgencycULus E19180 (JDXY1, JDYX7) / PSE JET5766
    Current rating10 A
    Voltage rating125 Vac
    Typical melting I2t145 A2s

    Practical Notes

    • Interrupting capability is 50 A at rated voltage, 50 Hz — confirm the circuit's prospective fault current stays below this.
    • Fast element suits resistive and semiconductor loads rather than motors with high inrush.
    • Because it opens within milliseconds, downstream semiconductors see less let-through energy.
    • Working voltage must stay at or below 125 Vac; a lower-rated part is not a safe substitute.
    • Do not upsize beyond 10 A to stop nuisance trips — fix the cause instead.

    Application Scenarios

    Common installation contexts include:

    • EV
    • surge

    Questions and Answers

    What are the ratings of the SR-5F-10A-AP?

    10 A continuous at 125 Vac, interrupting rating 50 A at rated voltage, 50 Hz.

    Is the SR-5F-10A-AP fast-acting or time-delay?

    It is fast-acting. Expect it to open quickly on overload.

    Can the SR-5F-10A-AP be used on a higher fault-current circuit?

    No — its interrupting rating is 50 A at rated voltage, 50 Hz. Choose a part whose breaking capacity exceeds the prospective fault current.