JCX-3E Eaton Bussmann 2400V 3A Class E Medium Voltage Fuse
JCX-3E Eaton Bussmann 2400V 3A Class E Medium Voltage Fuse

JCX-3E Eaton Bussmann 2400V 3A Class E Medium Voltage Fuse

Share
pEaton Bussmann JCX-3E, 2400V 3A Class E medium voltage fuse, 60 kAIC interrupting. For transformer, feeder and switchgear protection./p
    • Product Details
    • Download

    JCX-3E Eaton Bussmann 2400V 3A Class E Medium Voltage Fuse

    At a Glance
    • 2400 V rated voltage, 3 A rated current
    • 60 kAIC interrupting rating
    • Class E time-current characteristic
    • Single element

    The Eaton Bussmann JCX-3E is a medium voltage fuse with 2400 V rated voltage, 3 A rated current, 60 kAIC interrupting capacity, carrying a Class E time-current characteristic. Construction is 1 barrel, non indicating.

    Specifications

    General specifications
    UPC051712694223
    Product Length/Depth0.41 in
    Product Height1 in
    Product Width0.41 in
    Product Weight0.1 lb
    Electrical rating
    Amperage Rating3 A
    Interrupt rating60 kAIC
    Voltage rating2400 V
    Physical details
    Packaging typeStandard
    General information
    Barrels1
    ClassClass E
    ConnectionFerrule end x ferrule end
    ElementSingle
    Fuse indicatorNon Indicating

    Applications

    • Energy and utility distribution
    • Industrial equipment
    • Photovoltaic systems

    Selection Notes

    • Select against the available fault current at the installation point, not the load current — the interrupting rating has to exceed it with margin.
    • E-rated fuses follow a defined melting curve; pairing them with non-E-rated devices in the same feeder breaks coordination.
    • Termination: Ferrule end x ferrule end. Confirm the mating clip or busbar before ordering; ferrule and blade ends are not interchangeable.

    Common Questions

    What are the ratings of the Eaton Bussmann JCX-3E?
    2400 V / 3 A, with a 60 kAIC interrupting rating.
    How much fault current can the JCX-3E interrupt?
    60 kAIC. The available fault current at the installation point must not exceed this value.
    What does Class E mean for the JCX-3E?
    Class E defines the fuse's time-current characteristic. E-rated fuses carry a defined melting curve so they coordinate predictably with upstream and downstream devices; mixing E and non-E ratings in one feeder defeats that coordination.
    How does the JCX-3E connect?
    Ferrule end x ferrule end. Confirm the mating clip, holder or busbar before ordering — ferrule and blade ends are not interchangeable.
    How should I select the JCX-3E for a circuit?
    Match the voltage rating to the system voltage, keep the continuous current above the load current, and check that the interrupting rating exceeds the available fault current. In medium voltage work, select on the transformer or feeder fault level rather than the load current alone.

    Shenzhen Gaorunxin Technology Co., Ltd