JCY-2E Eaton Bussmann 5.5kV 2A Class E Medium Voltage Fuse
JCY-2E Eaton Bussmann 5.5kV 2A Class E Medium Voltage Fuse

JCY-2E Eaton Bussmann 5.5kV 2A Class E Medium Voltage Fuse

Share
pEaton Bussmann JCY-2E, 5.5kV 2A Class E medium voltage fuse, 60 kAIC interrupting. For transformer, feeder and switchgear protection./p
    • Product Details
    • Download

    JCY-2E Eaton Bussmann 5.5kV 2A Class E Medium Voltage Fuse

    At a Glance
    • 5.5 kV rated voltage, 2 A rated current
    • 60 kAIC interrupting rating
    • Class E time-current characteristic

    The Eaton Bussmann JCY-2E is a medium voltage fuse with 5.5 kV rated voltage, 2 A rated current, 60 kAIC interrupting capacity, carrying a Class E time-current characteristic.

    Series Selection Table

    JCY-2E series selection table
    Ampere ratings, dimensions and catalog numbers across the Medium Voltage Fuse family, reproduced from the Eaton Bussmann datasheet.

    Applications

    • Energy and utility distribution
    • Industrial equipment
    • Photovoltaic systems

    Selection Notes

    • Select against the available fault current at the installation point, not the load current — the interrupting rating has to exceed it with margin.
    • E-rated fuses follow a defined melting curve; pairing them with non-E-rated devices in the same feeder breaks coordination.

    Common Questions

    What are the ratings of the Eaton Bussmann JCY-2E?
    5.5 kV / 2 A, with a 60 kAIC interrupting rating.
    How much fault current can the JCY-2E interrupt?
    60 kAIC. The available fault current at the installation point must not exceed this value.
    What does Class E mean for the JCY-2E?
    Class E defines the fuse's time-current characteristic. E-rated fuses carry a defined melting curve so they coordinate predictably with upstream and downstream devices; mixing E and non-E ratings in one feeder defeats that coordination.
    How should I select the JCY-2E for a circuit?
    Match the voltage rating to the system voltage, keep the continuous current above the load current, and check that the interrupting rating exceeds the available fault current. In medium voltage work, select on the transformer or feeder fault level rather than the load current alone.