The Eaton Bussmann SF75X600BW is a semiconductor fuse rated 900V at 1100A and with a 80kA at 900V d.c., L/R 80ms interrupting rating. It is used for rectifiers, drives and inverters where the fuse must protect the diode or thyristor. 600A 900VDC, Traction Fuse, Bussmann Semiconductor Fuse.
| Product Name | Eaton Bussmann Traction Fuse |
| Catalog Number | SF75X600BW |
| Rated Amperage | 1100A |
| Rated Voltage | 900V |
| Product Length | 168mm |
| Product Height | 76mm |
| Product Width | 95mm |
| Product Weight | 1.5kg |
| Class | Class gR |
| Product Type | Traction fuse |
| Voltage Type | DC |
| Package Type | Standard |
| Breaking Capacity | 80kA at 900V d.c., L/R 80ms |
Rectifiers, drives and inverters where the fuse must protect the diode or thyristor.
Size the fuse on the semiconductor's I²t, not on the load current — the fuse must clear before the die is damaged.
Check the DC voltage derating: a fuse rated for AC duty often carries a lower DC rating.
What is the SF75X600BW rated for?
It is rated 900V at 1100A. The interrupting rating is 80kA at 900V d.c., L/R 80ms. It is a Class gR fuse.
What class is this fuse?
Class gR.
Can I replace it with a different class?
No. Fuse classes differ in dimensions and rejection features, so a different class will not fit the holder and may not provide the same protection.
What does the interrupting rating mean?
It is the maximum fault current the fuse can safely interrupt. It must be at least as high as the available fault current at the installation point.
How do I verify the part number?
Order by the full catalog number SF75X600BW; suffixes change the terminal, voltage or package.
Where can I find the datasheet?
The manufacturer datasheet is the authority for derating curves, I²t and agency approvals for this catalog number.
Source: manufacturer catalog page for SF75X600BW. Verify ratings against the current datasheet before ordering.
Shenzhen Gaorunxin Technology Co., Ltd